Installation Instructions For Monsoon Extra Pressure Sets:3.2 bar PS4.7 bar PSINDEX . . . . . . . . . . . . . . . . . Page NoApplication . . . . . .
- 10 -FusesThe following fuse size should be used with the appropriate pump:Wiring Of Connection UnitWARNING: This appliance must be earthed.The wire
- 11 -To enable correct assembly of the cable gland the ‘O’-ring (1) must be placed over the cable before the clamping insert (2) can be tightened.Not
- 12 -STEP 7 COMMISSIONINGWARNINGS: The motor casing can become very hot under normal operating conditions, care should be taken to ensure it c
- 13 -4. Pre-Start Check Always ensure the static inlet and outlet heads above the pump do not exceed the permitted maximum (see pump location s
- 14 -5. The pressure vessel air pre-charge does not require routine maintenance. Should ever the need arise for the vessel to have its air pre
- 15 -TROUBLE SHOOTING GUIDESymptoms Probable Cause Recommended ActionPump will not start. Water supply. Check water level in the supply tank and all
- 16 -Flow Switch Circuit Test1. First confirm visually that the flow switch reed clamp has not been dislodged during handling or installation.
- 17 -TECHNICAL SPECIFICATIONStuart Turner reserve the right to amend the specification in line with it’s policy of continuous development of its prod
- 18 -YOUR 2 YEAR GUARANTEEStuart Pumps are guaranteed by Stuart Turner Limited to be free from defects in materials or workmanship for the applicabl
- 19 -In the event of a claim please telephone Stuart Turner Limited on 0844 980 0097 or return your pump and flexible hoses with accessories removed,
- 2 -TYPICAL INSTALLATIONThe plumbing installation must comply with the following:The Water Supply (Water Fittings) Regulations 1999.BS6700 and buildi
Stuart Turner Ltd, Henley-on-Thames, Oxfordshire RG9 2AD ENGLAND Tel: +44 (0) 1491 572655, Fax: +44 (0) 1491 573704email: pumps@stuart-turn
- 3 -The pump must be installed so that the following conditions are met:Locate the pump in a frost free horizontal position where it cannot be spraye
- 4 -STEP 3 SEQUENCE OF OPERATIONThe pressure vessel is able to provide for small demands of water, limiting pump starts to the larger demand requirem
- 5 -Pipework Connections (Connection between pump and down-stream services to be boosted)This should run as far as possible in 22 mm copper tube. An
- 6 -Hose to Pipework1. Stuart Turner recommend only the use of their 22 mm flexible hoses. The hoses are fitted with plastic push-in connectors, wh
- 7 -4. Push pipe firmly into fitting, until pencil mark is level with the top of the collet and the pipe stop resistance is felt. Pull on pipe
- 8 -STEP 6 ELECTRICAL INSTALLATIONWARNINGS: The electrical installation must be carried out in accordance with the current national electrical
- 9 -The pressure set is factory fitted with a supplementary earthing wire to ensure continuity throughout the assembly (Fig. 10). It must be ensured