Installation, Operation & Maintenance InstructionsPlease leave this instruction booklet with the owner as it contains important guarantee, mainten
- 10 -4 ELECTRICAL INSTALLATION / EARTHING4.11 Regulations: The electrical installation must be carried out in accordance with the current na
- 11 -4.21 Wiring Diagrams:Model Fuse Size (AMPS)Monsoon Extra U1.4 bar 5All Models 134.22 Fuses: The following fuse size should be used with the a
- 12 -5.14 Starting: a) Ensure all outlets are closed, turn power supply ‘on’ - pump will start, pressurise the system then stop. b) Open
- 13 -Cont ...6 MAINTENANCE6.11 Turn off water supplies to the pump and release pressure by opening water outlets before attempting maintenanc
- 14 -Cont ... 6.14 Water scale: As water is heated scale deposits are released in areas of hard water, scale can cause the mechanical seal to
- 15 -Cont ...7 TECHNICAL SPECIFICATIONStuart Turner reserve the right to amend the specification in line with its policy of continuous development of
- 16 -8 TROUBLE SHOOTING GUIDESymptoms Probable Cause Recommended ActionPump will not start. Electrical supply. Check power supply.Check fuse (see fu
- 17 -Cont ...8.11 Dry Run Protection: This pump is fitted with a safety control circuit, which will detect the following fault condition: Dry r
- 18 -Cont ... Briefly reconnect the mains power supply to the pump – the ‘power on’ light should illuminate if the pump has been correctly wire
- 19 -9 THE MONSOON EXTRA GUARANTEECongratulations on purchasing a Stuart Turner pump. We are confident this pump will provide many years of trouble
- 2 -PRODUCT DESCRIPTIONElectric motor driven centrifugal pump complete with an automatic control system, consisting of flow switch, pressure switch,
DECLARATION OF CONFORMITY2006/42/ECBS EN ISO 12100-1, BS EN ISO 12100-2, BS EN 8092006/95/ECBS EN 60335-1, BS EN 60335-2-412004/108/ECBS EN 55014-1, B
- 3 -CHECKLISTNote: Item C & G are supplied loose and will require fitting to the pump inlet/outlet. Tighten to torque 4/5 Nm. Your product may
- 4 -Fig. 2Grub Screws(3 off)Outlet Tower can be swivelled at this joint line after loosening the 3 equi-spaced grub screwsPRE-INSTALLATION ASSEMBLY R
- 5 -Cont ...1 READ BEFORE COMMENCING PUMP INSTALLATIONA. Water storage capacity.1.11 The hot and cold water storage capacity (must be a minimum of
- 6 -Cont ...2 LOCATION - GENERAL2.11 Access: For emergencies and maintenance the pump must be easily accessible.2.12 Protection: The pump must
- 7 -2.26 Non-Preferred Pump Location: The pump must be located with at least 1 metre flooded suction at all times. If it is not possible to loc
- 8 -Cont ...Hot water connection:2.29 Hot water cylinder or storage tank: When a hot water cylinder or storage tank is used, ensure the pipewor
- 9 -Cont ...3 PUMP CONNECTIONS3.11 Hose to pump: These pumps have G 1 threaded connections to accept the hoses supplied. The hose end