2 LOCATION - GENERAL
2.11 Access: For emergencies and maintenance the pump must be
easily accessible.
2.12 Protection: The pump must be located in a dry position, frost free and
protected from freezing, particularly when installed in a loft (not
recommended).
2.13 Ventilation: Ensure an adequate air flow to cool the pump. Separate
the pump from other appliances that generate heat. An 80 mm (3 “) air
gap must be maintained around the pump.
2.14 Safety: The motor casing can become very hot under normal
operating conditions. Care must be taken to ensure it cannot be
touched during operation.
2.15 Water retention: Site the pump in a location where in the unlikely
event of a water leak, any spillage is contained or routed to avoid
electrics or areas sensitive to water damage.
2.16 Static inlet pressure: Before deciding where to locate the unit check to ensure
the static inlet head between pump and cold water level (Figs. 2 & 3) is at least 1
metre and does not exceed the max inlet head of 10 metres.
2.17 Pump position: The pump must be positioned on its anti-vibration mounting feet
and as close to the water source as possible.
2.18 Ambient temperature: The pump must be sited in a location where the maximum
ambient temperature does not exceed 50
o
C.
2.19 Pipework: For optimum performance pipework use 28 mm dia., 22 mm can be
used but will result in reduced pump performance.
Pipework should only reduce to 15 mm when entering terminal fitting.
2.20 Static outlet pressure: The static outlet head is indicated in Figs. 2 & 3.
2.21 Direction of flow: Ensure the water flow is in the direction of the arrow marked
on the flow switch reed clamp (vertically upwards).
2.22 Isolating valves: Separate isolating valves (non restrictive) must be fitted to
allow easy pump service.
2.23 Inline strainer: When pump is to be installed in areas where there is risk of
debris or scale build up within the system, you MUST ensure the inlet pipework is
fitted with an inline strainer.
2.24 Preferred pump location: The preferred pump location is below the water supply
connection that feeds the pump. The pump location is also dependent on
limitations of the static inlet and outlet heads of the installation. For guidance on
limitations and recommended location, consult the following relevant section for
hot or cold water installation.